Please wait a minute...
Frontiers of Electrical and Electronic Engineering

ISSN 2095-2732

ISSN 2095-2740(Online)

CN 10-1028/TM

Front Elect Electr Eng Chin    2010, Vol. 5 Issue (4) : 501-504    https://doi.org/10.1007/s11460-010-0096-9
RESEARCH ARTICLE
A magnetic detecting and evaluation method of substation’s grounding grids with break and corrosion
Yang LIU(), Xiang CUI, Zhibin ZHAO
School of Electrical and Electronic Engineering, North China Electric Power University, Baoding 071003, China
 Download: PDF(287 KB)   HTML
 Export: BibTeX | EndNote | Reference Manager | ProCite | RefWorks
Abstract

The grounding grid buried in the earth will become a hidden danger to the safety of substations due to some faults of breaks or thinner conductors in corrosion. A novel method to get accurate status of grounding grid was proposed based on measuring magnetic induction intensity. The basic structure of grounding grid without working drawing was concluded, and the positions and the status of faults were diagnosed by this method. The completed detecting system, including hardware device of data measurement, diagnosis, and analysis software, was introduced concisely. The results of simulations and applications show that this method is simple and effective in the practical engineering.

Keywords grounding grid      fault status      magnetic induction intensity      diagnosis     
Corresponding Author(s): LIU Yang,Email:hdwlly@163.com   
Issue Date: 05 December 2010
 Cite this article:   
Yang LIU,Xiang CUI,Zhibin ZHAO. A magnetic detecting and evaluation method of substation’s grounding grids with break and corrosion[J]. Front Elect Electr Eng Chin, 2010, 5(4): 501-504.
 URL:  
https://academic.hep.com.cn/fee/EN/10.1007/s11460-010-0096-9
https://academic.hep.com.cn/fee/EN/Y2010/V5/I4/501
Fig.1  Grounding grid of a 220 kV substation
Fig.2  Calculation results of . (a) Distributions of in the whole area; (b) distributions of in local area
Fig.3  Measuring systems
Fig.4  Coordinate series built by injecting point
Fig.5  Measuring results of magnetic induction intensities. (a) Distributions of of judging conductors in direction; (b) distributions of of judging conductors in direction
Fig.6  A grounding grids of a 110 kV substation
Fig.7  Distributions of surface magnetic induction intensities
1 Nikolakakos S. Corrosion and cathodic protection of steel grounding systems. Materials Performance , 1988, 27(7): 11–15
2 Lawson V R. Problems and detection of line anchor and substation ground grid corrosion. IEEE Transactions on Industry Applications , 1988, 24(1): 25–32
doi: 10.1109/28.87245
3 Hu J, Zeng R, He J L, Sun W M, Yao J X, Su Q. Novel method of corrosion diagnosis for grounding grid. In: Proceedings of International Conference on Power System Technology 2000 . 2000, 3: 1365–1370
4 Liu J, Wang J X, Wang S. An improved algorithm of corrosion diagnosis for grounding grids & its evaluation. Proceedings of the Chinese Society for Electrical Engineering , 2005, 25(3): 71–77 (in Chinese)
5 Zeng R, He J L, Hu J, Lu G J, Luo B. The theory and implementation of corrosion diagnosis for grounding system. In: Proceedings of Industry Applications Conference 2002 . 2002, 2: 1120–1126
6 Zhang B, Zhao Z B, Cui X, Li L. Diagnosis of breaks in substation’s grounding grid by using the electromagnetic method. IEEE Transactions on Magnetics , 2002, 38(2): 473–476
doi: 10.1109/20.996125
7 Dawalibi F P. Electromagnetic fields generated by overhead and buried short conductors. Part 2 — Ground networks. IEEE Transactions on Power Delivery , 1986, 1(4): 112–119
doi: 10.1109/TPWRD.1986.4308037
8 Liu Y, Cui X, Zhao Z B, Qi L, Chen J J. Method of corrosion diagnosis of substations’ grounding grids based on electromagnetic induction theory. Proceedings of the Chinese Society for Electrical Engineering , 2009, 29(4): 97–103 (in Chinese)
9 Liu Y, Cui X, Zhao Z B. Method for diagnosing the conductor broken point of grounding grids in substation based on measuring the magnetic induction intensity. High Voltage Engineering , 2008, 34(7): 1389–1394 (in Chinese)
10 Liu Y., Cui X., Zhao Z B. Design and application of exciting power for substation grounding grids testing system based on impedance transformation technology. Proceedings of the Chinese Society for Electrical Engineering , 2008, 28(28): 18–23 (in Chinese)
11 Liu Y, Cui X, Zhao Z B, Li L, Chen J J. Design and application of testing magnetic field system for corrosion diagnosis of grounding grids in substation. Transactions of China Electrotechnical Society , 2009, 24(1): 176–182 (in Chinese)
[1] Biao SUN, Peter B. LUH, Zheng O’NEILL. SPC and Kalman filter-based fault detection and diagnosis for an air-cooled chiller[J]. Front Elect Electr Eng Chin, 2011, 6(3): 412-423.
[2] HUANG Jin, NIU Faliang, YANG Jiaqiang. Induction motor rotor fault diagnosis method based on double PQ transformation[J]. Front. Electr. Electron. Eng., 2007, 2(1): 117-122.
[3] NIU Fa-liang, HUANG Jin, YANG Jia-qiang, CHEN Li-yuan, JIN Hai. Rotor broken-bar fault diagnosis of induction motor based on HHT of the startup electromagnetic torque[J]. Front. Electr. Electron. Eng., 2006, 1(2): 188-193.
Viewed