New refrigeration system using CO vapor-solid as refrigerant
New refrigeration system using CO vapor-solid as refrigerant
HUANG Dongping1, DING Guoliang1, QUACK Hans2
1.Institute of Refrigeration and Cryogenics Engineering, Shanghai Jiao Tong University; 2.Institute of Refrigeration and Cryogenics Technology, Technical University of Dresden
Abstract:A refrigerant must be in the vapor-liquid phase in a vapor-compression refrigeration system, therefore, CO2 cannot be used as a refrigerant for temperatures lower than -56°C because solid CO2 will form under the triple point temperature of -56°C. A refrigeration system with CO2 vapor-solid particles as refrigerant is put forward, by which a temperature lower than the triple point is achieved. An adjustable nozzle, a sublimator, a high-pressure regulating valve and a low-pressure regulating valve are used to replace the conventional evaporator. Theoretical cycle analysis of the refrigeration system shows that its COP can be 50% higher than that of the conventional one.
出版日期: 2008-12-05
引用本文:
. New refrigeration system using CO vapor-solid as refrigerant[J]. Frontiers of Energy and Power Engineering in China, 2008, 2(4): 494-498.
HUANG Dongping, DING Guoliang, QUACK Hans. New refrigeration system using CO vapor-solid as refrigerant. Front. Energy, 2008, 2(4): 494-498.
Lorentzen G . Revivalof carbon dioxide as a refrigerant, Part 1. H & V Engineer, 1993, 66(721): 9–14
2
Lorentzen G . Revivalof carbon dioxide as a refrigerant, Part 2. H & V Engineer, 1993, 66(722): 10–12
3
Pearson A . Ammonia/CO2 refrigeration system breaks new ground. Refrig Air Cond, 2002, 104(1): 23–25
4
Forbes P S . Ammonia-carbon dioxide cascade system. DKV-Tagungsbericht Bremen, 2000, 27(1): 49–53
5
Gebhardt H . Nestlesetzt auf NH3 und den Kaeltetraeger CO2. Kaelte und Klimatechnik, 2001, 11(1): 50–55
6
Barry. . Supermarketsbuy into CO2 refrigerant systems. Refrig Air Cond, 2002, 104(1): 29–38
7
Rozhentsev A V . A throttle-sublimation refrigerating machine using the solid coolantwith changeable porous structure. Proceedings of 19th Internationalcongress of refrigeration. Paris: InternationalInstitute of Refrigeration, 1995, 176–183
8
Span R, Wagner W . A new equation of state forcarbon dioxide covering the fluid region from the triple-point temperatureto 1100 K at pressure up to 800 MPa. JPhy Chem Ref Data, 1996, 25(6): 1509–1595
9
Huang Dongping, Ding Guoliang, Quack Hans . Experimental study of blockage during throttling releaseof CO2 under high pressure. Journal of Shanghai Jiaotong University, 2006, 40(8): 1417–1421
10
Bracco F V . Modeling of engine sprays. SAE Paper, 1985-850394