Frontiers in Energy  2013, Vol. 7 Issue (3): 399-405   https://doi.org/10.1007/s11708-013-0260-z
  RESEARCH ARTICLE 本期目录
Comparison and analysis of energy consumption of energy-efficient office buildings in different climate regions in China: case studies
Comparison and analysis of energy consumption of energy-efficient office buildings in different climate regions in China: case studies
Ke ZHANG(), Neng ZHU
School of Environmental Science and Engineering, Tianjin University, Tianjin 300072, China
 全文: PDF(283 KB)   HTML
Abstract

The purpose of this paper is to analyze the energy consumption (EC) and find out the determining factors of energy-efficient office building cases according to specific case studies in typical cities of different climate zones in China. The investigated building cases were located in four cities (Beijing, Ningbo, Nanjing and Shenzhen) of three architecture thermotechnical design zones (cold zone, hot summer and cold winter zone, hot summer and warm winter zone). The analysis indicates that the energy consumption index (ECI) of these four cases ranges from 41.06 to 74.23 kW·h/(m2·a). Besides, the outdoor climate can change the EC of air conditioning/heating systems, and further determine the monthly volatility of the total EC of the whole building.

Key wordsenergy-efficient building    breakdown energy consumption (EC)    energy consumption index (ECI)    different climate zone
收稿日期: 2012-11-10      出版日期: 2013-09-05
Corresponding Author(s): ZHANG Ke,Email:zdzk111@163.com   
 引用本文:   
. Comparison and analysis of energy consumption of energy-efficient office buildings in different climate regions in China: case studies[J]. Frontiers in Energy, 2013, 7(3): 399-405.
Ke ZHANG, Neng ZHU. Comparison and analysis of energy consumption of energy-efficient office buildings in different climate regions in China: case studies. Front Energ, 2013, 7(3): 399-405.
 链接本文:  
https://academic.hep.com.cn/fie/CN/10.1007/s11708-013-0260-z
https://academic.hep.com.cn/fie/CN/Y2013/V7/I3/399
Climate zoneCold zoneHot summer and cold winter zoneHot summer and warm winter zone
CityBeijingNingboNanjingShenzhen
Building No.B1N2N3S4
Con year (Retrofit)20051992(1996)20072009
Building typeOffice buildingOffice and lodgingOffice buildingComprehensive green office building
GFA/m221044.654760.0021773.9018170.00
Basement area/m27714.5106751.796000.00
Cooling season5.15-9.155.15-10.154.1-10.314.1-11.15
Heating season11.15-3.1511.1-3.3111.1-3.31
Heating sourceMunicipal hot water 95/70°CSplit AC unitVRV local turbine
Cooling sourceCentrifugal chillersSplit AC unitVRV local turbineWSPH+ cooling tower+ VRV
Air conditioning systemPrimary air fancoil systemSplit AC unitVRV+ DOASFCU+ capillary radient cooling+ VRV+ DOAS
Building structure formGlass block screen wallMasonry structureGlass block screen wallRC shear wall
Insulation situationNoYesYesNo
Tab.1  
Building No. (2010)B1N2N3S3
GFA/m221044.654760.0021262.4718170.00
No. of workers3501200430
Electricity/(kW·h·a-1)1173500339638.048729841091613
Gas/(m3· a-1)25536192000
Hot water (95/70°C)/(kg·a-1)4004000000
Total/(kW·h·a-1)1382651.246353329.568729841091613
ECIa)65.7074.2341.0660.08
ECIb)3950.43727.492538.63
Tab.2  
Energy using systemsUsing area/m2EC/(kW·h·a-1)Percentage/%ECI/(kW·h·m-2·a-1)
Heating8529.1952457.164.476.15
Cooling8529.19309048.226.3436.23
Blower176.119775.060.8355.51
Cooking613.0719550.131.6731.89
Lighting and office equipment19154.89737427.562.8438.5
Elevator21044.654887.5330.420.23
Information equipment room92.8940354.353.44434.43
Tab.3  
Energy using systemsUsing area/m2EC/(kW·h·a-1)Percentage/%ECI/(kW·h·m-2·a-1)
Heating282986478.5624.57%30.57
Cooling282973888.9221.00%26.12
Domestic hot water131549649.2014.11%37.76
Blower14596864.001.95%4.70
Cooking29636505.303.89%46.26
Lighting430140138.2611.41%9.33
Indoor equipment285030362.738.63%10.65
Other equipment73422813.7814.45%69.26
Tab.4  
Energy using systemsUsing area/m2EC/(kW·h·a-1)Percentage/%ECI/(kW·h·m-2·a-1)
Heating89391833612120.51
Cooling893922992826.3425.72
Blower4028.87269243.086.68
Lighting and office equipments13478.129466933.7521.86
Elevator13478.1688707.895.11
Facilities in equipment room13478.1269103.081.96
Service equipment13478.1161721.851.18
Tab.5  
Energy use systemsUsing area/m2EC/(kW·h·a-1)Percentage/%ECI/(kW·h·m-2·a-1)
Cooling930028847827.65%31.02
Power plant200542121.304.04%21.01
Pump200544928.004.31%22.41
Elevator1599533696.003.23%2.11
Cooking30013968.401.34%46.56
Lighting1599520044.831.92%1.25
Office facilities15995215228.520.63%13.46
Information equipment room50152186.0014.59%3043.72
Laboratory1279164924.0015.81%128.95
Control room32667607.006.48%207.38
Tab.6  
Fig.1  
Fig.2  
Fig.3  
Fig.4  
1 Hong T Z, Jiang Y. Low energy healthy building and sustainable development. HVAC , 1996, 27(6): 28–31 (in Chinese)
2 Wan K K W, Li D H W, Liu D L, Lam J C. Future trends of building heating and cooling loads and energy consumption in different climates. Building and Environment , 2011, 46(1): 223–234
doi: 10.1016/j.buildenv.2010.07.016
3 Ren H B, Zhou W S, Gao W J. Optimal option of distributed energy systems for building complexes in different climate zones in China. Applied Energy , 2012, 91(1): 156–165
doi: 10.1016/j.apenergy.2011.08.044
4 Li D H W, Yang L, Lam J C. Impact of climate change on energy use in the built environment in different climate zones-A review. Energy , 2012, 42(1): 103–112
doi: 10.1016/j.energy.2012.03.044
5 Lam J C, Wan K K W, Tsang C L, Yang L. Building energy efficiency in different climates. Energy Conversion and Management , 2008, 49(8): 2354–2366
doi: 10.1016/j.enconman.2008.01.013
6 Lam J C, Tsang C L, Yang L. Impacts of lighting density on heating and cooling loads in different climates in China. Energy Conversion and Management , 2006, 47(13,14): 1942–1953
7 Wan K K W, Li D H W, Yang L, Lam J C. Climate classifications and building energy use implications in China. Energy and Building , 2010, 42(9): 1463–1471
doi: 10.1016/j.enbuild.2010.03.016
8 Xiao H, Wei Q P. Discussion on method of energy consumption survey and statistics in existing public buildings. HVAC , 2010, 40(3): 12–18 (in Chinese)
9 Yang L, Lam J C, Liu J P. Analysis of typical meteorological years in different climates of China. Energy Conversion and Management , 2007, 48(2): 654–668
doi: 10.1016/j.enconman.2006.05.016
10 Ministry of Housing and Urban-Rural Deveiopment of the People’s Republic of China, General Administration of Quality Supervision, Inspection and Quarantine. GB50176-93 Thermal Design Code for Civil Buildings. Beijing: China Architecture &Building Press, 1993
11 Ministry of Housing and Urban-Rural Deveiopment of the People’s Republic of China, General Administration of Quality Supervision, Inspection and Quarantine. GB50365-2005 Design Standard for Energy Efficiency of Public Buildings. Beijing: China Architecture &Building Press, 2005
12 Jiang Y, Liu X H, Xue Z F, Fu L. Study on ECC index of energy conversion system. Energy of China , 2004, 26(3): 27–31 (in Chinese)
13 Yi J, Yang X. In the energy analysis using the electricity equivalent method. Energy of China , 2010, 32(5): 5–11 (in Chinese)
14 Xue Z F. Energy Saving Diagnosis and Transformation for Existing Buildings. Beijing: China Architecture & Building Press, 2007 (in Chinese)
Viewed
Full text


Abstract

Cited

  Shared   
  Discussed