Frontiers in Energy  2014, Vol. 8 Issue (3): 386-393   https://doi.org/10.1007/s11708-014-0323-9
  本期目录
Parameter identification of interconnected power system frequency after trip-out of high voltage transmission line
Xuzhan ZHOU1,Shanshan LIU2,Mingkun WANG2,Yiping DAI2,*(),Yaohua TANG1
1. Electrical Power Research Institute of Henan Electric Power Corporation, Zhengzhou 450052, China
2. School of Energy & Power Engineering, Xi’an Jiaotong University, Xi’an 710049, China
 全文: PDF(610 KB)   HTML
Abstract

Accurate modeling and parameters of high voltage (HV) grid are critical for stability research of system frequency. In this paper, simulation modeling of the system frequency was conducted of an interconnected power system with HV transmission lines in China. Based on recorded tripping data of the HV transmission lines, system parameters were identified by using genetic algorithm (GA). The favorable agreement between simulation results and recorded data verifies the validity of gird models and the accuracy of system parameters. The results of this paper can provide reference for the stability research of HV power grid.

Key wordshigh voltage (HV) grid    frequency stability parameter identification    primary frequency regulation (PFR)
收稿日期: 2013-12-06      出版日期: 2014-09-09
Corresponding Author(s): Yiping DAI   
 引用本文:   
. [J]. Frontiers in Energy, 2014, 8(3): 386-393.
Xuzhan ZHOU,Shanshan LIU,Mingkun WANG,Yiping DAI,Yaohua TANG. Parameter identification of interconnected power system frequency after trip-out of high voltage transmission line. Front. Energy, 2014, 8(3): 386-393.
 链接本文:  
https://academic.hep.com.cn/fie/CN/10.1007/s11708-014-0323-9
https://academic.hep.com.cn/fie/CN/Y2014/V8/I3/386
Fig.1  
Fig.2  
Fig.3  
Parametervalue
TO/s0.1
TC/s0.3
T1/s0.02
TH/s0.3
TR/s12
TL/s0.6
FH0.3
FI0.4
FL0.3
Tab.1  
Fig.4  
Fig.5  
Fig.6  
Fig.7  
Fig.8  
Fig.9  
Fig.10  
ParameterGrid BGrid C
λi0.40.6
δi0.0720.097
τi/s0.561.06
Mi/s12.213.2
KLi1.361.02
T124.734.73
Tab.2  
Fig.11  
ParameterValue
δ/s0.035
τ/s1.06
M/s19.7
KL0.915
Tab.3  
1 Liu Z Y. The Ultra High Voltage Grid. Beijing: China Economic Publishing House, 2005 (in Chinese)
2 Scherer H N, Vassell G S. Transmission of electric power at ultra-high voltages: current status and future prospects. Proceedings of the IEEE, 1985, 73(8): 1252–1278
doi: 10.1109/PROC.1985.13280
3 Saccomanno F. Electric Power Systems Analysis and Control. New York: IEEE Press, 2003
4 Liu H, Wu T, Wang M N. Theoretical analysis of two-area interconnected system tie-line power oscillation. In: 2011 International Conference on Electrical and Control Engineering. Yichang, China, 2011, 5621–5624
5 Hong F, Chen J, Duan X, Xi J, Ling W, Li Y, Jiang M. Research on tie line power flow oscillation in weak interconnection power grids. Proceedings of the CSEE, 2011, 31(10): 1–6 (in Chinese)
6 Gao L, Dai Y, Ma Q, Zhang L. Research on stability of primary frequency regulation of interconnected power system after trip-out of ultra high voltage transmission line. Power System Technology, 2009, 33(20): 27–32 (in Chinese)
7 Zhao T, Dai Y, Gao L. Research on the primary frequency control characteristics of generators in power system. In: 2nd IEEE Conference on Industrial Electronics and Applications. Harbin, China, 2007, 569–574
8 Nangsue P, Pillay P, Conry S E. Evolutionary algorithms for induction motor parameter determination. IEEE Transactions on Energy Conversion, 1999, 14(3): 447–453
doi: 10.1109/60.790895