Please wait a minute...
Frontiers in Energy

ISSN 2095-1701

ISSN 2095-1698(Online)

CN 11-6017/TK

Postal Subscription Code 80-972

2018 Impact Factor: 1.701

Front. Energy    2008, Vol. 2 Issue (1) : 43-47    https://doi.org/10.1007/s11708-008-0005-6
Thermodynamic performance experiment and cooling number calculation of a counter-flow spray humidifier in the HAT cycle
WANG Yuzhang, LI Yixing, WENG Shilie, WANG Yonghong
School of Mechanical Engineering, Key Laboratory for Power Machinery and Engineering of Ministry of Education P. R. China, Shanghai Jiaotong University;
 Download: PDF(163 KB)   HTML
 Export: BibTeX | EndNote | Reference Manager | ProCite | RefWorks
Abstract An experimental investigation of the thermodynamic performance of a counter-flow spray humidifier was conducted on the basis of theoretical analysis of the heat and mass transfer mechanism inside the humidifier. Critical parameters such as the temperature and relative humidity of air and the temperature of water at the inlet and outlet were measured. The influence of every measured parameter on the thermal performance of the humidifier was obtained under different experimental conditions. The cooling number, whose variation was also obtained, was calculated according to the measured data. The experimental results show that both the temperature and the temperature increment of outlet humid air and the temperature of outlet water increase with an increase of the water-gas ratio, whereas the cooling number decreases. Under all experimental conditions, the outlet humid air reaches or is close to the saturation level. The lower cooling number is favorable for the system, but it has an optimal value for a certain humidifier.
Issue Date: 05 March 2008
 Cite this article:   
LI Yixing,WANG Yuzhang,WENG Shilie, et al. Thermodynamic performance experiment and cooling number calculation of a counter-flow spray humidifier in the HAT cycle[J]. Front. Energy, 2008, 2(1): 43-47.
 URL:  
https://academic.hep.com.cn/fie/EN/10.1007/s11708-008-0005-6
https://academic.hep.com.cn/fie/EN/Y2008/V2/I1/43
1 Rao A D Processfor producing powerUS Patent, 4829763 1989
2 Xiao Y H Cai R X Lin R M Modeling HAT cycle and thermodynamic evaluationEnergy Conversion and Management 1997 38(15–17)16051612
3 Jonsson M Yan J Humidified gas turbines-a reviewof proposed and implemented cyclesEnergy 2005 3010131078
4 Parente J O S Traverso A Massardo A F Saturator analysis for an evaporative gas turbine cycleApplied Thermal Engineering 2003 2312751293
5 Paolo C Giovanni L Ennio M Assessment of the thermodynamic performance of mixed gas-steamcycles: Part B: Water-injected and hat cyclesASME Journal of Engineering for Gas Turbines and Power 1995 117499508
6 Wang Y Z Wang Y H Jin M Y Development of new experiment system of countercurrenthumidifierGas Turbine Technology 2004 17(2)4145 (in Chinese)
7 Shi Y J Operationand Experiment of Cooling TowerBeijingWater and Electric Power Press 1990 (in Chinese)
8 Wang Y Z Li Y X Weng S L Experimental investigation on inner two-phase flow in counter-flowspray saturator for HAT cycleApplied ThermalEngineering 2006 17–1824172424
9 Wang Y Z Li Y X Weng S L Su M Experimentalinvestigation on humidifying performance of counter-flow spray saturatorfor humid air turbine cycleEnergy Conversion &Management 2007 48(3)756763
10 Li Y X Wang Y Z Weng S L et al.Development of a new temperature measuring systemfor gas-liquid flow in spraying fieldExperimentalThermal and Fluid Science 2007 31(8)917924
Viewed
Full text


Abstract

Cited

  Shared   
  Discussed