Evaluation of the performance of a centralized ground-water heat pump system in cold climate region
Shilei LU1,*(),Zhe CAI1,Li ZHANG2,Yiran LI1
1. School of Environmental Science and Engineering, Tianjin University, Tianjin 300072, China
2. China Aerospace Construction Group Co., Ltd., Beijing 100071, China
 全文: PDF(949 KB)   HTML
Abstract

The aim of this study is to evaluate the performance of a centralized open-loop ground-water heat pump (GWHP) system for climate conditioning in Beijing with a cold climate in China. Thus, a long-time test was conducted on a running GWHP system for the heating season from December 2011 to March 2012. The analysis of the testing data indicates that the average heat-pump coefficient of performance (COP) and the COP of the system (COPs) are 4.27 and 2.59. The low value and large fluctuation in the range of COP are found to be caused by the heat transfixion in the aquifer and the bypass in the circulation loop. Therefore, some suggestions are proposed to improve the performance for GWHPs in the cold climate region in China.

Key wordsground-water heat pump (GWHP)    actual coefficient of performance    heat transfixion
收稿日期: 2013-11-28      出版日期: 2014-09-09
Corresponding Author(s): Shilei LU   
 引用本文:   
. [J]. Frontiers in Energy, 2014, 8(3): 394-402.
Shilei LU,Zhe CAI,Li ZHANG,Yiran LI. Evaluation of the performance of a centralized ground-water heat pump system in cold climate region. Front. Energy, 2014, 8(3): 394-402.
 链接本文:  
https://academic.hep.com.cn/fie/CN/10.1007/s11708-014-0310-1
https://academic.hep.com.cn/fie/CN/Y2014/V8/I3/394
Climate ValuesMonth
JanFebMarAprMayJunJulAugSepOctNovDec
Average outdoor temp/°C-3.8-1.67.714.419.424.526.525.620.412.95.4-0.5
Maximum outdoor temp/°C0.84.011.921.423.42930.631.328.118.19.95.6
Minimum outdoor temp/°C-9.9-7.70.27.013.115.923.222.615.66.9-0.1-7.1
Average relative humidity/%42.739.434.749.958.956.679.174.165.555.655.645.4
Total solar radiation/(MJ·m-2·d-1)253.4336.3463.6542.5594.5567.1531.4513.6400.8357.8263.8217.3
Average wind velocity/(m·s-1)2.62.43.02.82.42.42.01.92.02.02.12.5
Tab.1  
Fig.1  
NameSemi-hermetic screw ground water heat pump unit
Product typeLSBLGR-1400M
Refrigerating capacity/kW1104
Input power of cooling/kW220
Flow of chilled water/(m3·h-1)220
Flow of cooling water/(m3·h-1)251
Heating capacity/kW1569
Power input of heating/kW279
Flow of cold water/(m3·h-1)194
Flow of hot water/(m3·h-1)243
Unit dimension/m4465×1640×2118
Tab.2  
Fig.2  
NameType and specificationNumberNote
Circulating loop pumpsType: QPG200-315Flow: 242 m3/hPump head: 27 mPower: 37 kW4Totally 4 pumps are installed, of which 1 is a spare unit
Immersible pumpType: KQL200/285-37/4Flow: 362 m3/hPump head: 24 mPower: 37 kW3Installed in well 1#、2#、4#
Tab.3  
Measurement itemsTest intervalTest devicesRangeMeasurement accuracy
Water temperatureInlet and outlet of the evaporator10 minTR004 temperature sensor-30-125°C±0.5°C
Inlet and outlet of the condenser
Inlet and outlet of the circulation loop
Inlet and outlet of the ground water loop
FlowEvaporator10 minZRN-100 ultrasonic flowmeter1%
Condenser
Circulation loop
Ground water loop
Air temperatureIndoor air10 minTR002 temperature sensor-20-70°C±0.7°C
Outdoor air
Power consumptionHeat-pump unit10 minpower meter
System1day
Tab.4  
Temperature of ground water/°CTemperature difference of ground water loop/°CFlow of ground water/(m3·h-1)Temperature of supply water/°CTemperature difference of circulation water loop/°CFlow of circulation water loop/(m3·h-1)
Average value14–194–860–150441.5–4.5210–230
Design value155194455243
Tab.5  
Fig.3  
Fig.4  
Fig.5  
Fig.6  
Fig.7  
Gc/m3·h-1)Ge/m3·h-1)Tc,o/°CTe,i /°CCOP
220504014.54.41
158504014.54.46
220503814.54.70
158503814.54.72
220503614.54.99
158503614.55.03
Tab.6  
Gc/(m3·h-1)Ge/(m3·h-1)Tc,o/°CTe,i/°CCOP
220504018.05.02
220504016.54.80
220504014.54.41
Tab.7  
Fig.8  
Fig.9  
Fig.10  
Fig.11  
1 Bilen K, Ozyurt O,Bakirci K, Karsli S, Erdogan S, Yilmaz M, Comakli O. Energy production, consumption, and environmental pollution for sustainable development: a case study in Turkey. Renewable and Sustainable Energy Reviews, 2008, 12(6), 1529–1561
2 Sun X G. Engineering Technology and Management of Ground Source Heat Pump. Beijing: China Architecture & Building Press, 2009 (in Chinese)
3 Zhang Y A, Li B. Application analysis on open-loop surface water-source heat-pump systems. Heating Ventilating & Air Conditioning, 2007, 37(9): 99–104 (in Chinese)
4 Mustafa Omer A. Ground-source heat pumps systems and applications. Renewable and Sustainable Energy Reviews, 2008, 12(2): 344–371
5 Stefano Lo Russoa, Glenda Taddiaa , Vittorio Verdab. Development of the thermally affected zone (TAZ) around a groundwater heat pump (GWH. P) system: a sensitivity analysis. Geothermics, 2012, (7): 66–74
6 Xue Y Q, Xie C H, Zhang Z H, Wu J C. Study on numerical modeling of 3-D aquifer thermal energy storage with transient flow. Geological Review, 1994, 40(1): 74–81(in Chinese)